NFPA 70E 130.7(C)(7) / Table 130.7(C)(7)(a)
What it means on the job
When performing energized electrical work such as voltage testing on a 480V MCC, voltage-rated insulating gloves with leather protectors are required. Class 00 or Class 0 gloves are minimum for 480V work, and the shock protection boundaries must be observed.
Tested in 1 CraftIQ puzzle
- whats-wrongUnion Hall Training: Arc Flash PPE Assessment
Related NFPA sections
NFPA 68 / NFPA 484 / OSHA 1910.94
Aluminum dust is highly combustible and explosive. Dust collectors handling combustible metals must have explosion relief vents sized per NFPA 68 to safely relieve deflagration pressure. Without relief venting, an internal dust explosion can rupture the collector, sending shrapnel and flame into the facility.
NFPA 70E 110.4(B) / 120.1
Damaged test lead insulation can expose the user to electrical shock and can cause phase-to-phase or phase-to-ground short circuits resulting in arc flash. All test equipment must be inspected before each use per NFPA 70E and replaced if damaged.
NFPA 70E 130.7(C)(10)
A standard face shield does not provide arc-rated protection for the face and neck. Category 3 requires an arc-rated balaclava worn under an arc-rated face shield and hard hat to protect exposed skin from arc flash burns.
NFPA 70E Table 130.7(C)(15)(a)
The incident energy analysis on the arc flash label indicates Category 3 hazard. Wearing Category 1 PPE (4 cal/cm²) provides dangerously insufficient protection for a Category 3 exposure (25 cal/cm²). PPE category must meet or exceed the hazard level.
NFPA 72 Section 21.3.5 / IBC 907.3.3
NFPA 72 Section 21.3.5 (Elevator Recall for Fire Fighters' Service) and IBC 907.3.3 (Elevator recall) require smoke detection in elevator machine rooms, machinery spaces, hoistways, and lobbies to initiate elevator recall (Phase I) per NFPA 72 and ASME A17.1. Without a smoke detector, the elevator recall system cannot activate automatically, potentially sending cars to a fire floor and trapping occupants in a smoke-filled hoistway. (Note the code book: elevator recall is IBC 907.3.3 / IFC 606-607, not IBC Chapter 6, which covers Types of Construction.)
NFPA 75 Section 8.5 / NFPA 2001 Section 4.2.4
This fails code. NFPA 75 Section 8.5 and NFPA 2001 Section 4.2.4 require pre-discharge notification in occupied or occupiable spaces before clean agent release. Audible alarms and visible strobes must activate to provide adequate warning time for personnel to evacuate. A manual abort switch must also be provided so that a pending discharge can be cancelled if the alarm is determined to be false. Even rooms that are typically unoccupied still require these safeguards because maintenance personnel may be present at any time. Without pre-discharge alarms, personnel could be exposed to reduced oxygen concentrations during discharge.