ASHRAE Guideline 36 — Damper/Fan Interlocks

What it means on the job

An end switch or position feedback must confirm the motorized outside air damper is fully open before the evaporator fan is allowed to start. Starting the fan with the damper closed creates high negative pressure in the ductwork and starves the unit of ventilation air, potentially damaging ductwork and causing inadequate outdoor air delivery.

Tested in 1 CraftIQ puzzle

  • whats-wrongMotorized Outside Air Damper Interlock
Practice this code — free

Related ASHRAE sections

ASHRAE Guideline 13, Specifying Building Automation Systems (advisory) — applied through the project BAS specification, Division 25

The installed sensors meet the specification. ASHRAE Guideline 13 (advisory, applied via the project BAS specification) recommends space temperature sensors with accuracy of +/- 0.5 degrees F or better for zone control. The 10K thermistor is a standard sensor type for DDC systems, providing adequate accuracy for HVAC zone control.

ASHRAE Guideline 36 — Chiller Staging

Staging a lag chiller immediately at 100% lead capacity causes hunting and instability. A time delay (typically 10-15 minutes) and sustained load confirmation are required to prevent short-cycling. ASHRAE Guideline 36 specifies staging criteria with time delays and load verification.

ASHRAE Guideline 36 — Cooling Coil Control

Cooling coil control valves should fail closed (spring return to closed) on loss of signal or power. Failing open causes uncontrolled cooling and potential freezing of downstream coils or spaces.

ASHRAE Guideline 36 — Freeze Protection

A freeze stat alarm must automatically shut down the AHU fan, close the outdoor air damper, and open the heating valve. An alarm-only response without automatic action risks coil freeze-up and catastrophic water damage.

ASHRAE Guideline 36 — High-Performance Sequences of Operation

The DP sensor is located at the pump discharge instead of at the most remote coil or 2/3 of the way out in the system. Sensing DP at the pump header causes the VFD to maintain artificially high system pressure, defeating the purpose of variable flow. The sensor must be relocated to represent the actual system load point.

ASHRAE Guideline 36 — Monitoring Requirements

Temperature trend data should have at least 0.1 degree resolution. Whole-number-only resolution (e.g., 72 vs. 72.3) loses critical information needed for analyzing control loop performance, setpoint drift, and energy optimization.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.