ASHRAE Guideline 36 — Cooling Coil Control
What it means on the job
Cooling coil control valves should fail closed (spring return to closed) on loss of signal or power. Failing open causes uncontrolled cooling and potential freezing of downstream coils or spaces.
Tested in 1 CraftIQ puzzle
- whats-wrongControl Valve Actuator Setup
Related ASHRAE sections
ASHRAE Guideline 13 — Alarm Management
Alarms must be prioritized based on severity. A freeze stat alarm (life-safety) should be higher priority than a dirty filter alarm (maintenance). Without prioritization, critical alarms get lost in nuisance alarms, a condition called 'alarm flooding'.
ASHRAE Guideline 13 — Data Management
Storing trend data only in field controllers risks data loss when controllers are reset or lose power. Trend data should be archived to the BAS server or a dedicated historian. Controller memory is limited and will overwrite oldest data.
ASHRAE Guideline 36 — Chiller Staging
Staging a lag chiller immediately at 100% lead capacity causes hunting and instability. A time delay (typically 10-15 minutes) and sustained load confirmation are required to prevent short-cycling. ASHRAE Guideline 36 specifies staging criteria with time delays and load verification.
ASHRAE Guideline 36 — Damper/Fan Interlocks
An end switch or position feedback must confirm the motorized outside air damper is fully open before the evaporator fan is allowed to start. Starting the fan with the damper closed creates high negative pressure in the ductwork and starves the unit of ventilation air, potentially damaging ductwork and causing inadequate outdoor air delivery.
ASHRAE Guideline 36 — Freeze Protection
A freeze stat alarm must automatically shut down the AHU fan, close the outdoor air damper, and open the heating valve. An alarm-only response without automatic action risks coil freeze-up and catastrophic water damage.
ASHRAE Guideline 36 — High-Performance Sequences of Operation
The DP sensor is located at the pump discharge instead of at the most remote coil or 2/3 of the way out in the system. Sensing DP at the pump header causes the VFD to maintain artificially high system pressure, defeating the purpose of variable flow. The sensor must be relocated to represent the actual system load point.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.