NEC 708.22

What it means on the job

This fails code. NEC Article 708 (Critical Operations Power Systems) Section 708.22 (Capacity of Power Sources) requires the alternate power source to be sized for a minimum of 72 hours (3 days) of full-load operation of the Designated Critical Operations Area. The 24-hour supply provides only about 33% of the required minimum run time. The 72-hour requirement exists because during major disasters such as hurricanes, earthquakes, or ice storms, fuel delivery infrastructure can be disrupted for days or even weeks. A COPS facility must be capable of sustaining critical operations independently during extended emergencies, regardless of assumptions about local fuel delivery availability. Management convenience or cost considerations do not override this code requirement.

Tested in 1 CraftIQ puzzle

  • code-checkNEC 708 — COPS Facility Without 72-Hour Fuel Supply
Practice this code — free

Related NEC sections

NEC 645.5(E)(2)(5)

The deciding fact is the fire suppression system, not the airflow. NEC 645.5(E)(2)(4) PERMITS Types CL2, CL3, CM and CMG under a raised floor where the air space is protected by an automatic fire suppression system — the normal condition in a modern data hall. Only where that space is NOT protected does 645.5(E)(2)(5) narrow the allowance to substitute Type CMP. Article 645 exists precisely to relax the ordinary plenum-cable rule inside a qualifying IT equipment room, so reaching for the general rule here gets it backwards.

NEC 700.10(B)(1)

NEC 700.10(B)(1) requires emergency circuit wiring to be kept entirely independent of all other wiring and equipment. Routing emergency and normal power in the same raceway means a single fire or physical damage event can disable both systems simultaneously, eliminating the redundancy that emergency power provides.

NEC 700.32 / 701.27

NEC requires selective coordination of overcurrent protective devices for emergency systems, legally required standby systems, and critical operations power systems. Without it, a fault on one circuit can trip upstream devices, blacking out the entire system.

NEC 725.136

Low-voltage thermostat wire must maintain separation from line-voltage wiring. Running parallel causes electromagnetic interference that can damage the thermostat or cause erratic operation.

NEC 760.49 / IBC 909.11

NEC 760.49 and IBC 909.11 require fire alarm circuits serving smoke control functions to use fire-rated wiring (2-hour rated CI cable or wiring in 2-hour rated enclosures). Standard fire alarm cable that burns through in the first minutes of a fire will disable smoke damper control precisely when it is needed most.

NEC Article 725.136(A)

Low-voltage sensor wiring (Class 2) must be run in separate conduit from line-voltage power wiring per NEC Article 725.136(A). Electromagnetic interference from the 120V power induces noise on the sensor signal, causing erratic readings and unstable control loops on the new DDC system.