NEC 314.29

What it means on the job

All junction boxes, pull boxes, and conduit bodies must remain accessible without removing any part of the building structure. Boxes cannot be buried behind walls, ceilings, or floors.

Tested in 1 CraftIQ puzzle

  • whats-wrongJunction Box Issues
Practice this code — free

Related NEC sections

NEC 250.64(C)

Grounding conductor splices must use listed connectors such as split bolts, compression connectors, or exothermic welds. Electrical tape alone is not a listed grounding connection method.

NEC 314.16(B)

Box fill calculations per NEC 314.16 require each #12 conductor to have 2.25 cu in. An overfilled box causes conductor damage, overheating, and difficulty making proper connections.

NEC 314.16(B)(1)-(B)(5)

This box is OVERFILLED, so it is not compliant. Per NEC 314.16(B), each #14 AWG insulated conductor counts as 2.0 cu in (6 conductors = 12.0). Per 314.16(B)(2) all internal clamps together count as one allowance (2.0). Per 314.16(B)(5) all equipment grounding conductors together count as one allowance (2.0). Critically, per NEC 314.16(B)(4) a device yoke counts as TWO volume allowances based on the largest conductor connected to it: 2 x 2.0 = 4.0 cu in — not one. Total = 12.0 + 2.0 + 2.0 + 4.0 = 20.0 cu in required, which exceeds the 18.0 cu in box by 2.0 cu in. A larger box (or fewer conductors) is required.

NEC 358.26

The maximum number of bends between pull points cannot exceed 360 degrees (four 90-degree bends). Exceeding this limit makes wire pulling extremely difficult and risks damaging conductor insulation.

NEC 400.8

Window AC units must be plugged directly into a wall outlet, never an extension cord. Extension cords cause voltage drop, overheating, and are a fire hazard with high-amperage equipment.

NEC 406.12(1)

All 125-volt, 15- and 20-ampere receptacles in dwelling-unit bathrooms must be listed tamper-resistant. A standard (non-TR) receptacle is a violation. (Note: a 15A receptacle is itself permitted on a 20A circuit serving two or more receptacles per Table 210.21(B)(3) — the defect here is the missing tamper-resistant listing, not the amperage.)