NEC 314.16(B)
What it means on the job
Box fill calculations per NEC 314.16 require each #12 conductor to have 2.25 cu in. An overfilled box causes conductor damage, overheating, and difficulty making proper connections.
Tested in 1 CraftIQ puzzle
- whats-wrongJunction Box Issues
Related NEC sections
NEC 250.32(B)
This is correct. In a sub-panel (whether in the same building or a separate structure with a 4-wire feeder), the neutral must be isolated from the equipment grounding conductor and the enclosure. Bonding neutral to ground at a sub-panel creates parallel paths for return current, which can put current on metal parts and create shock hazards. The bonding is done only at the main panel (service equipment).
NEC 250.53(D)(2)
A metal underground water pipe electrode must be supplemented by an additional grounding electrode. It cannot serve as the sole grounding electrode because plastic pipe repairs can interrupt the path.
NEC 250.64(C)
Grounding conductor splices must use listed connectors such as split bolts, compression connectors, or exothermic welds. Electrical tape alone is not a listed grounding connection method.
NEC 314.16(B)(1)-(B)(5)
This box is OVERFILLED, so it is not compliant. Per NEC 314.16(B), each #14 AWG insulated conductor counts as 2.0 cu in (6 conductors = 12.0). Per 314.16(B)(2) all internal clamps together count as one allowance (2.0). Per 314.16(B)(5) all equipment grounding conductors together count as one allowance (2.0). Critically, per NEC 314.16(B)(4) a device yoke counts as TWO volume allowances based on the largest conductor connected to it: 2 x 2.0 = 4.0 cu in — not one. Total = 12.0 + 2.0 + 2.0 + 4.0 = 20.0 cu in required, which exceeds the 18.0 cu in box by 2.0 cu in. A larger box (or fewer conductors) is required.
NEC 314.29
All junction boxes, pull boxes, and conduit bodies must remain accessible without removing any part of the building structure. Boxes cannot be buried behind walls, ceilings, or floors.
NEC 358.26
The maximum number of bends between pull points cannot exceed 360 degrees (four 90-degree bends). Exceeding this limit makes wire pulling extremely difficult and risks damaging conductor insulation.