NEC 250.118 / 250.122 / 406.4(C)

What it means on the job

Even though UF cable includes a grounding conductor, if individual conductors are run in conduit underground, an equipment grounding conductor of a recognized type must be included and sized with the circuit so the receptacle has an effective ground-fault current path.

Tested in 1 CraftIQ puzzle

  • whats-wrongOutdoor Receptacle Installation
Practice this code — free

Related NEC sections

NEC 230.95

NEC 230.95 requires ground-fault protection for equipment (GFPE) on services rated 1,000A or more at 480V. In a high-rise electrical riser, a ground fault without GFPE can cause an arcing fault that escalates into a fire within the riser shaft, potentially disabling power to multiple floors before being detected.

NEC 240.86 / high-rise office Specification

The high-rise commercial office specification explicitly prohibits series rating of overcurrent protective devices. All existing panels being re-utilized must use fully rated breakers — meaning each individual breaker must have an interrupting rating equal to or exceeding the available fault current at the panel (22kAIC in this case). Series rating is prohibited because in a multi-tenant high-rise, a fault that exceeds a branch breaker's interrupting rating could cause catastrophic breaker failure, arc flash, and damage to adjacent tenants' electrical systems. The branch breaker must be replaced with one rated at minimum 22kAIC.

NEC 250.102

Flexible metal conduit in this size/length is not a reliable ground path; an equipment bonding jumper or an EGC must be run to bond the motor.

NEC 250.118 / 410.44

Suspended ceiling support wires and grid members are not listed as equipment grounding conductors. A separate equipment grounding conductor or grounding path must be provided for all lighting fixtures.

NEC 250.118(5)

Flexible metal conduit over 6 feet in length requires an equipment bonding jumper. Even under 6 feet, the FMC connections must provide a reliable ground path, and many jurisdictions require a bonding jumper regardless of length.

NEC 250.146(D) / high-rise office Electrical Plans

Data rooms require isolated ground (IG) receptacles to prevent electromagnetic interference from the building's general grounding system from affecting sensitive electronic equipment. The high-rise office plans specifically call out IG receptacles for data room locations.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.