NEC 110.26(A)(1)
What it means on the job
NEC 110.26(A)(1) requires a minimum 3 ft (36 in) depth of clear working space in front of equipment likely to be examined, adjusted, or serviced while energized. A 208Y/120V secondary is 120 volts to ground, which lands in the 0-150V row of Table 110.26(A)(1) — and that row is 3 ft under Conditions 1, 2 and 3 alike, so it does not matter how the rack opposite is classified. Thirty inches is six inches short either way. This is the rule that gets squeezed hardest in a data hall, because every inch of white space is a cabinet somebody wanted to sell — but the working space exists so an electrician can open that PDU and get clear of it. Working space is measured from the live parts or the enclosure face, and separately, NEC 110.26(B) requires it be kept clear at all times and never used for storage.
Tested in 2 CraftIQ puzzles
- whats-wrongResidential Panel Installation
- code-checkWorking Space in Front of a PDU
Related NEC sections
NEC 110.14(A)
Unless the breaker is listed and labeled for two conductors, only one conductor per terminal is allowed. Double-tapping causes loose connections and overheating.
NEC 110.14(A) / UL Listing
While backstab connections are technically allowed for 14 AWG, they are unreliable on 12 AWG 20A circuits and are a leading cause of loose connections and arcing. Screw terminals or clamp-type connections are required for 12 AWG.
NEC 110.26(A)
NEC 110.26(A) requires a minimum of 36 inches of clear working space in front of electrical equipment, 30 inches wide (or the width of the equipment, whichever is greater), and from the floor to a height of 6.5 feet or the height of the equipment, whichever is greater. 18 inches is a serious violation. The space must be kept clear at all times for safe access during emergencies.
NEC 110.26(A)(1) / 110.26(A)(3)
This installation fails on multiple counts. NEC 110.26(A)(1) requires a minimum depth of 36 inches of clear working space measured from the exposed live parts or the front of the enclosure. With only 28 inches between the panel and the water heater, this is 8 inches short of the 36-inch minimum. Even the 30-inch width measurement is at the bare minimum per NEC 110.26(A)(2). Additionally, NEC 110.26(A)(3) requires the working space to extend from the floor to a height of 6 feet 6 inches or the height of the equipment, whichever is greater. IBEW training emphasizes that working clearance violations are the most commonly cited NEC violation on inspections — an electrician needs room to safely operate breakers and escape in an emergency.
NEC 110.26(A)(2)
Working-space width must be at least 762 mm (30 in.) OR the full width of the equipment, whichever is greater. A 1200A switchboard section is wider than 30 in., so 30 in. of clear width does not span the equipment and is insufficient. (There is no amperage-based 36-in. width rule — 36 in. is the Condition-1 working-space depth.)
NEC 110.26(D)
Working space around service equipment rated 600V or less requires illumination. An electrician must be able to see clearly when operating breakers or performing maintenance.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.