NEC 110.14(A) / UL Listing

What it means on the job

While backstab connections are technically allowed for 14 AWG, they are unreliable on 12 AWG 20A circuits and are a leading cause of loose connections and arcing. Screw terminals or clamp-type connections are required for 12 AWG.

Tested in 1 CraftIQ puzzle

  • whats-wrongKitchen Receptacle Wiring
Practice this code — free

Related NEC sections

NEC 110.14(A)

Unless the breaker is listed and labeled for two conductors, only one conductor per terminal is allowed. Double-tapping causes loose connections and overheating.

NEC 110.26(A)

NEC 110.26(A) requires a minimum of 36 inches of clear working space in front of electrical equipment, 30 inches wide (or the width of the equipment, whichever is greater), and from the floor to a height of 6.5 feet or the height of the equipment, whichever is greater. 18 inches is a serious violation. The space must be kept clear at all times for safe access during emergencies.

NEC 110.26(A)(1)

NEC requires a minimum of 36 inches of clear working space in front of electrical panels for safe access and operation.

NEC 110.26(A)(1) / 110.26(A)(3)

This installation fails on multiple counts. NEC 110.26(A)(1) requires a minimum depth of 36 inches of clear working space measured from the exposed live parts or the front of the enclosure. With only 28 inches between the panel and the water heater, this is 8 inches short of the 36-inch minimum. Even the 30-inch width measurement is at the bare minimum per NEC 110.26(A)(2). Additionally, NEC 110.26(A)(3) requires the working space to extend from the floor to a height of 6 feet 6 inches or the height of the equipment, whichever is greater. IBEW training emphasizes that working clearance violations are the most commonly cited NEC violation on inspections — an electrician needs room to safely operate breakers and escape in an emergency.

NEC 110.26(A)(2)

Working-space width must be at least 762 mm (30 in.) OR the full width of the equipment, whichever is greater. A 1200A switchboard section is wider than 30 in., so 30 in. of clear width does not span the equipment and is insufficient. (There is no amperage-based 36-in. width rule — 36 in. is the Condition-1 working-space depth.)

NEC 110.26(D)

Working space around service equipment rated 600V or less requires illumination. An electrician must be able to see clearly when operating breakers or performing maintenance.