EJMA Standards / Manufacturer Installation Guide

What it means on the job

Shipping restraint bars/rods must be removed after installation and before system operation. Leaving them in prevents the joint from absorbing expansion, transferring all stress to anchors and equipment.

Tested in 1 CraftIQ puzzle

  • whats-wrongExpansion Joint Installation
Practice this code — free

Related OTHER sections

Crestline VFD Specification / NEMA MG-1 Part 31

Crestline specifications limit VFD output cable length to a maximum of 20 feet without specific engineer approval and additional mitigation. Long cable runs cause voltage reflections (reflected wave phenomenon) that can double the peak voltage at motor terminals, destroying motor winding insulation.

Crestline VFD Specification / NFPA 70

At 15 feet, the cable length is within the 20-foot maximum allowed without engineer approval. Short cable runs minimize reflected wave voltage spikes that can damage motor winding insulation. VFD output pulses travel along the cable and reflect at the motor terminals — longer cables create higher voltage peaks. The proper shielded cable and correct shield grounding at both ends also helps contain electromagnetic interference (EMI). If the run needed to exceed 20 feet, an output reactor or dV/dt filter would be required.

EJMA Standards / ASME B31.1 Section 119

Bellows expansion joints require pipe guides on both sides to ensure axial movement only. Without guides, lateral forces can distort the bellows and cause premature failure.

Engineering practice (ASME B31.3 §314.2.2 permits, does not mandate)

A thermowell lets the sensor be removed or replaced without breaching the pressure boundary or shutting the line down. A directly inserted element makes every instrument replacement a process opening and exposes the sensor to erosion and full process pressure. Note the standing of this one: it is established engineering and maintenance practice rather than an ASME B31.3 mandate — B31.3 mentions thermometer wells only as a permitted specialty threaded component, it never requires one.

FGI Guidelines 2.2-3.1 / ASHRAE 170

FGI Guidelines Section 2.2-3.1 and ASHRAE 170 require operating rooms to maintain positive pressure relative to adjacent corridors. Propping the door open defeats the positive pressure relationship, allowing corridor contaminants to enter the sterile field. Studies show each OR door opening increases airborne colony-forming units by 15-30%.

high-rise office Base Building Standard / ASHRAE 90.1 Energy Metering

The high-rise office specification requires a BTU meter on each CRAC unit per base building standard, tied to the building management system (BMS). Without a BTU meter, the tenant cannot be accurately billed for cooling energy consumption, and the base building owner has no visibility into the MDF cooling load for capacity planning.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.