ASHRAE 90.1-2019 Section 6.5.3.4 (supply-air-temperature reset)
What it means on the job
This passes. ASHRAE 90.1-2019 Section 6.5.3.4 requires multiple-zone HVAC systems to reset supply air temperature in response to either representative building loads OR outdoor air temperature, by at least 25 percent of the difference between the design SAT and the design room temperature. The scheduled reset from 55 degrees F at 90 degrees F OAT up to 65 degrees F at 60 degrees F OAT is a 10-degree reset driven by outdoor air temperature — an explicitly permitted method that meets the code minimum. Zone-based Trim-and-Respond reset (ASHRAE Guideline 36) is a voluntary best-practice guideline, not adopted code, so its preference cannot make an otherwise-compliant outdoor-air reset fail inspection. Only if the project specification specifically mandated G36 zone-based reset would the OAT method be non-compliant — and the spec would have to state that.
Tested in 1 CraftIQ puzzle
- code-checkSupply Air Temperature Reset
Related ASHRAE sections
ASHRAE 90.1 Section 6.5.4.2 (6.5.4.1 in the 2016 edition) — Hydronic Variable Flow Systems
The VFD is in bypass mode despite being fully functional, meaning the pump runs at constant full speed. This eliminates the energy savings from variable flow operation. At 50% flow, a VFD-controlled pump uses only ~12.5% of full-speed power (affinity laws). Running in bypass at full speed wastes substantial energy and creates excessive pressure in the system.
ASHRAE 90.1 Table 6.8.3-1
Per ASHRAE 90.1 Table 6.8.3-1, a 4-inch hot-water pipe (NPS 4 falls in the '4 to <8 inch' column) operating in the 141-200°F fluid band requires a minimum of 2.0 inches of insulation. At 200°F the pipe is in that band, so the 1.5 inches of fiberglass installed is below the 2.0-inch minimum — the pipe is under-insulated and the installation fails. (1.5 inches would only satisfy the requirement for pipe smaller than 1.5 inches in this temperature band.) The fix is to bring the insulation up to at least 2.0 inches for a 4-inch pipe at this fluid temperature.
ASHRAE 90.1-2019 Section 6.4.3.4.2 (shutoff damper controls) / high-rise office Mechanical Specification
The high-rise office specification requires the motorized outside air damper to be interlocked with evaporator fan operation. The damper must open only when the fan is running and close when the fan stops. A timeclock-only schedule creates two problems: (1) if the fan trips or fails during occupied hours, the damper remains open, allowing unconditioned outdoor air into the space; (2) if the timeclock schedule does not match actual fan operation (overtime, holidays), the damper may be open with no fan running. The interlock ensures the damper state always matches the fan state, satisfying the project specification and the ASHRAE 90.1-2019 Section 6.4.3.4.2 shutoff-damper requirement that outdoor-air dampers automatically close when the system serving the space is not in use.
ASHRAE 90.1-2019 Section 6.5.4.2 (Hydronic Variable Flow Systems)
ASHRAE 90.1-2019 Section 6.5.4.2 (Hydronic Variable Flow Systems) requires that any HVAC pumping system with a total pump system power exceeding 10 HP that uses modulating control valves be designed for variable flow — capable of reducing pump flow to 50% or less of design — and three-way valves are explicitly not acceptable. The trigger is pump system power, not chiller tonnage, but a 500-ton plant's chilled water pumps are far above 10 HP, so the requirement plainly applies. The constant-flow arrangement with 3-way valves and no pump VFDs violates it. The system must be redesigned with 2-way control valves at all coils, variable frequency drives on chilled water pumps, differential pressure sensors for pump speed control, and a minimum flow bypass to protect chiller evaporators at low loads. Constant-flow systems at this scale waste enormous pumping energy, particularly at the part-load conditions that represent the vast majority of annual operating hours.
ASHRAE 90.1-2019 Section 6.5.4.2 (Hydronic Variable Flow Systems) / ASHRAE Handbook — HVAC Systems and Equipment
This is a fully code-compliant primary-only variable flow chilled water design that meets ASHRAE 90.1-2019 requirements. The 2-way control valves allow flow to vary with load, the VFDs on pumps reduce energy consumption at part load, and the differential pressure sensor at the most remote coil ensures the pumps maintain only the minimum pressure needed to serve all loads. The minimum flow bypass valve set at 30% of design flow protects the chiller evaporators from low-flow conditions that could cause freezing or laminar flow issues. This design is the current industry-preferred approach as it eliminates the need for separate primary and secondary pumping loops, reducing both first cost and operating energy compared to traditional primary-secondary systems.
ASHRAE 90.1-2019 Section 6.5.5.2 (Heat Rejection Equipment — Fan Speed Control)
ASHRAE 90.1-2019 Section 6.5.5.2 (Fan Speed Control) requires that each fan on heat-rejection equipment (cooling towers, closed-circuit coolers, evaporative condensers) powered by a motor of 7.5 HP or larger have controls that automatically change fan speed — a two-speed motor, a variable-speed drive, or other approved modulating control. The trigger is the fan motor horsepower, not the condenser-water flow rate. This 30 HP single-speed fan is well above the 7.5 HP threshold, so simple on/off contactor control violates the requirement. A single-speed fan cycling on and off also wastes significant energy and causes large swings in condenser water temperature, reducing chiller efficiency. Variable-speed control is preferred because fan power varies with roughly the cube of speed — operating at 80% speed uses only about 51% of full-load power. A VFD on the cooling tower fan typically pays for itself within one to two cooling seasons through reduced energy consumption.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.