NFPA 99, Section 5.1.12

What it means on the job

Medical gas piping must pass two distinct pressure tests with oil-free dry nitrogen before patient use: an initial pressure test at 1.5 times the system working pressure (and not less than 150 psi) to check every joint, then a separate 24-hour standing pressure test at 20% above normal operating line pressure. Purging and cross-connection verification follow.