NEC 501.125(B)

What it means on the job

This is code-compliant. NEC 501.125(B) explicitly permits the installation of open or nonexplosionproof enclosed motors — such as squirrel-cage induction motors WITHOUT brushes, switching mechanisms, or similar arc-producing devices — in Class I, Division 2 locations. Explosionproof or totally-enclosed construction is NOT required for these motors in Division 2. An ODP squirrel-cage induction motor with no normally-arcing components is precisely the type the code allows, and the engineer's reasoning is sound: Division 2 means a flammable concentration is present only under abnormal conditions, and a brushless induction motor has no arc source during normal operation. The only conditions are that the motor has no arc-producing devices (satisfied here) and that its maximum external surface temperature not exceed the temperature limit (T-code / 80% of the gas group autoignition temperature). The scenario states no over-temperature condition, so the installation passes. (Had the scenario specified a surface temperature exceeding the gas AIT limit, it would fail — but as written it does not.)

Tested in 1 CraftIQ puzzle

  • code-checkNEC 500 — Standard Motor in Class I, Division 2 Area
Practice this code — free

Related NEC sections

NEC 480.9(A) / NFPA 1 52.3.3

VRLA and flooded lead-acid batteries emit hydrogen gas during charging. Without dedicated ventilation, hydrogen can accumulate to explosive concentrations (4% LEL). Mechanical ventilation is required per NEC 480.9(A) (Ventilation) and NFPA 1 52.3.3.

NEC 500.8 / NFPA 497 Chapter 5

Disconnect switches within the classified hazardous area boundary of a flammable liquid dispensing point must be rated for the area classification. NEC Table 514.3 and NFPA 497 define the extent of classified areas around dispensing points. A non-rated switch can produce arcs that ignite flammable vapors.

NEC 501.10(B) / NEC 501.15

All conduit fittings in Class I, Division 2 locations must be listed for the specific hazardous classification. Standard fittings can allow ignitable concentrations of gas to migrate through the conduit system. NEC 501.10(B) requires conduit seals and listed fittings to prevent gas migration and potential ignition.

NEC 501.15(A)

NEC 501.15(A) requires conduit seals at every point where conduit passes from a Class I, Division 1 or 2 area into an unclassified area. Without the seal, flammable gases or vapors can migrate through the conduit system into unclassified areas, creating an explosion hazard in spaces not designed for it.

NEC 501.15(A)(1)

The seal is in the right place conceptually but too far away. NEC 501.15(A)(1) requires a conduit seal within 18 inches of an enclosure containing an arcing or sparking device in a Class I Division 1 location. The seal exists to stop an explosion inside the enclosure from propagating down the raceway to the rest of the system, and to keep gases from migrating along the conduit. Six inches over the limit is still a violation. The 'no fitting between the seal and the enclosure' part is correct and is the other half of the same rule.

NEC 517.13 / NFPA 99 Section 6.3.3.2

NEC 517.13 and NFPA 99 Section 6.3.3.2 require the impedance of the grounding path in patient care areas to not exceed 0.1 ohms. At 0.5 ohms, the grounding path has five times the allowable resistance, which means fault currents will clear more slowly and voltage on equipment enclosures could reach levels dangerous to patients.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.