NEC 430.72

What it means on the job

A motor control circuit tapped from the branch-circuit conductors must be protected against overcurrent per the control-circuit rules; an unprotected tap is a fire risk.

Tested in 1 CraftIQ puzzle

  • whats-wrongPump Motor Branch Circuit
Practice this code — free

Related NEC sections

NEC 430.1 / NFPA 90A / high-rise office Electrical Plans

Motorized dampers and motorized shades shown on the high-rise office electrical plans must be connected to the appropriate branch circuits with proper control wiring. Unconnected motorized dampers can prevent proper smoke control in a high-rise fire event, creating a life-safety hazard.

NEC 430.102(B)

A disconnecting means must be located within sight of the motor it controls so a technician can lock it out for service. None is provided here.

NEC 430.32

Each motor must have overload protection to prevent damage from sustained overcurrent. Overloads are separate from the branch circuit short-circuit protection and are typically sized at 115-125% of motor FLA.

NEC 440.14

NEC 440.14 requires the disconnecting means to be within sight from and readily accessible from the air-conditioning or refrigerating equipment. 'Within sight' (or 'In Sight From') per NEC Article 100 means the equipment is visible AND not more than 50 feet distant. The scenario satisfies both: the disconnect is visible from the unit and only 30 feet away (under the 50-foot limit), and it is readily accessible on the exterior wall. There is NO NEC requirement that the disconnect be on the 'same level' as the equipment or that the servicer never leave the rooftop — a wall-mounted disconnect that is visible, within 50 feet, and readily accessible is fully compliant. The installation meets 440.14.

NEC 445.18 / NFPA 110 7.2

An emergency stop accessible from outside the generator room is required so operators can shut down the generator without entering a potentially hazardous space (fire, fuel leak, or excessive noise). NEC 445.18 requires a readily accessible disconnecting means.

NEC 460.8 / VFD Manufacturer Guidelines

Power factor correction capacitors must never be installed on the output side of a VFD. The capacitors resonate with the VFD's PWM switching frequency, causing destructive overcurrents that will fail the capacitors and potentially damage the drive. Capacitors go on the input side only.