NEC 210.11(C)(3)

What it means on the job

NEC 210.11(C)(3) requires at least one 20A branch circuit to supply bathroom receptacle outlets. This circuit is permitted to supply receptacles in multiple bathrooms. The key restriction is that no other outlets (lights, exhaust fans, etc.) from other rooms can be on this circuit — it must serve only bathroom receptacles. GFCI protection is separately required by NEC 210.8(A)(1).

Tested in 2 CraftIQ puzzles

  • whats-wrongBathroom Receptacle Circuit
  • code-checkBathroom Circuit Sharing
Practice this code — free

Related NEC sections

NEC 110.26(A)(2)

Working-space width must be at least 762 mm (30 in.) OR the full width of the equipment, whichever is greater. A 1200A switchboard section is wider than 30 in., so 30 in. of clear width does not span the equipment and is insufficient. (There is no amperage-based 36-in. width rule — 36 in. is the Condition-1 working-space depth.)

NEC 110.26(D)

Working space around service equipment rated 600V or less requires illumination. An electrician must be able to see clearly when operating breakers or performing maintenance.

NEC 110.27 / NFPA 70E

Battery cabinets must remain closed to prevent accidental contact with live DC bus bars and to contain any thermal event. Open cabinets also violate NEC 110.27 regarding guarding of live parts and create arc flash hazards.

NEC 210.12(A)

This installation is fully code-compliant. NEC 210.12(A) requires AFCI protection for all 120V, 15A and 20A branch circuits supplying outlets and devices in dwelling unit bedrooms. A 15A combination-type AFCI breaker with 14 AWG wiring is correctly matched (NEC Table 310.16 rates 14 AWG at 15A). Tamper-resistant receptacles are required per NEC 406.12 in all dwelling unit locations. This is a textbook installation that IBEW halls use as a baseline example of proper bedroom circuit design.

NEC 210.19(A) Informational Note / high-rise office Single Line Diagram

This branch circuit EXCEEDS the enforced 3% maximum, so it is not compliant. Calculation (single-phase): Vd = 2 x I x R x L / 1000 = 2 x 20A x 1.93 x 85 / 1000 = 6.56V. The circuit is 120V nominal, so VD% = 6.56V / 120V x 100 = 5.47% — NOT 2.7% (2.7% only results from erroneously dividing by 240V, the wrong nominal for a 120V circuit). At 5.47% the drop exceeds both the project-enforced 3% branch maximum and the NEC 210.19(A) Informational Note 3% recommendation. To meet 3% (3.6V max) at 20A over 85 ft would require roughly 8 AWG copper, or the load/length must be reduced.

NEC 210.20(A)

NEC 210.20(A) requires that continuous loads (3+ hours, which applies to IT equipment) not exceed 80% of the branch circuit breaker rating. Loading to 95% will cause nuisance tripping and violates the continuous load derating requirement.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.