IPC 706.3
What it means on the job
Sanitary tees may only be used for vertical-to-horizontal transitions. For horizontal-to-horizontal connections, a wye with 45-degree bend or combination wye-bend must be used to maintain proper flow.
Tested in 1 CraftIQ puzzle
- whats-wrongResidential DWV Drain Line
Related IPC sections
IPC 608.16.4 / ASSE 5013
The relief port discharge must terminate with an air gap above any drain receptor. Without an air gap, a cross-connection is created at the very device meant to prevent cross-connections. The discharge must also be visible to indicate when the relief valve is operating.
IPC 704.1
For pipes 3 inches and larger, the minimum slope is 1/8 inch per foot. A slope of 1/4 inch per foot exceeds the minimum and is acceptable. While the minimum would suffice, a steeper slope within reason provides better flow velocity and self-scouring action.
IPC 705.5
ABS and PVC cannot be joined with solvent cement. These dissimilar plastics require a listed mechanical coupling (such as a banded no-hub coupling) or approved transition fitting.
IPC 708.3
This cleanout layout meets IPC requirements. Cleanouts are required at the base of stacks, at each aggregate change of direction greater than 135 degrees (45 degrees from straight), and at maximum 100-foot intervals for 4-inch and larger drains (75 feet for smaller drains). The installation is compliant.
IPC 802.1
This installation is correct. Ice machines, food-handling equipment, and similar appliances must discharge through an indirect waste connection to prevent sewage backflow from contaminating food or ice. The 2-inch air gap exceeds the minimum requirement (1 inch or two times the pipe diameter, whichever is greater) and ensures a physical break between the fixture drain and the sanitary system. This is one of the first cross-connection control lessons taught at the UA hall — if it makes food or ice, it gets an air gap.
IPC 905.2
The vent connection must be above the trap weir (the overflow point of the trap). Connecting below the weir makes it a wet vent carrying waste, not a true vent, and will not properly protect the trap seal.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.