IMC Section 701 / IFGC Section 304.6

What it means on the job

This installation fails on multiple counts. First, when combustion air is drawn directly from outdoors using natural ventilation, the IMC and IFGC require TWO openings — one within 12 inches of the ceiling and one within 12 inches of the floor — to create natural convective air circulation. Only one opening is provided. Second, each opening must be sized at a minimum of 1 square inch per 4,000 BTU/hr of total input rating. For a 2,000,000 BTU/hr boiler: 2,000,000 / 4,000 = 500 square inches minimum per opening. The single 144 square inch opening is drastically undersized even if it were the only requirement. The room needs two openings of at least 500 square inches each (approximately 20 inches x 25 inches) to provide adequate combustion air for safe boiler operation.