International Fuel Gas Code
The IFGC covers fuel-gas piping, appliance connections, venting, and combustion air. These are the IFGC sections CraftIQ tests.
7 sections explained
IFGC 304
Gas furnaces in confined spaces require combustion air openings — one high and one low — to ensure adequate air for safe combustion. Without it, the furnace can produce CO.
IFGC 404.11 (Protection against corrosion)
Field-applied polyethylene tape is not an approved corrosion-protection system for underground steel gas pipe. Per IFGC 404.11, steel IS permitted underground only when it has a factory-applied, electrically insulating coating AND a cathodic protection system that is monitored and maintained (zinc galvanizing is not recognized as adequate). This install has neither, so it fails — the problem is the missing coating/cathodic protection, not the use of steel itself. The common alternative is PE (polyethylene) plastic, with the steel-to-PE transition (anodeless riser) made before the pipe enters the building, since PE is not permitted inside structures. Note: fuel-gas piping is governed by the IFGC, not the IPC.
IFGC 404.3
Gas piping must not be installed in or through any air duct, clothes chute, chimney, vent, dumbwaiter, or elevator shaft. A leak inside a duct would distribute gas throughout the building.
IFGC 408.4
Gas piping to equipment must have a sediment trap (drip leg) to catch moisture and debris before it enters the gas valve. Prevents valve damage and unsafe operation.
IFGC 408.4 / IPC 1212.7
A sediment trap (drip leg) must be installed as close as practical to the appliance inlet and ahead of the gas valve. It captures moisture and debris that could damage the gas valve.
IFGC 503.6.5
Single-wall vent connectors must slope upward at least 1/4" per foot toward the chimney or vent terminal. Downward slope traps condensate and prevents proper draft.
IFGC Section 304.6.1 and 304.6.2 (Outdoor combustion air)
The free AREA is what fails here, not the opening count — and that distinction matters in front of an inspector. IFGC 304.6 permits outdoor combustion air by EITHER method: 304.6.2 (One-permanent-opening) allows a SINGLE opening near the enclosure top at 1 in² per 3,000 Btu/h given 1 in. side/back and 6 in. front appliance clearances, which for 2,000,000 Btu/h needs 667 in². 304.6.1 (Two-permanent-openings) uses one opening within 12 in. of the top and one within 12 in. of the bottom, each at 1 in² per 4,000 Btu/h = 500 in² (or 1 in² per 2,000 Btu/h = 1,000 in² each if horizontal ducts are used). The 144 in² provided fails every one of those paths by a wide margin. Note these are FREE areas — per IFGC 304.10 louver and grille blockage is deducted, so the gross wall opening is larger still. So "only one opening" is NOT by itself a violation; the undersizing is.
Practice these sections
Every section above is tested by real CraftIQ puzzles — spot violations, pass inspections, and learn why. Free for apprentices.
Start practicing — free