Crestline Valve Specification / MSS SP-110

What it means on the job

These ball valves meet all specification requirements for 2-inch and smaller service. The 600 PSI rating meets the requirement for ball valves 2 inches and smaller. Full-port design ensures minimal pressure drop and allows full flow capacity — a reduced port valve would restrict flow and create an unacceptable pressure drop. The PTFE (Teflon) seat material provides excellent chemical resistance, low friction, and is compatible with chilled water temperatures. The 600 PSI rating at 42°F operating temperature provides substantial safety margin over the 125 PSI system pressure.

Tested in 1 CraftIQ puzzle

  • code-checkBall Valve Specification for Small Piping
Practice this code — free

Related OTHER sections

Crestline Seismic Specification

This is correct. Per Crestline spec, in-line duct equipment weighing 75 pounds or less is considered seismically braced by the duct system itself, provided it is rigidly attached to the duct. At 65 pounds, the humidifier is under the 75-pound threshold. The duct's own seismic bracing (transverse at 30 ft max, longitudinal at 60 ft max) provides adequate restraint for the lightweight equipment. If the humidifier exceeded 75 pounds, it would require independent seismic supports regardless of its duct connection.

Crestline Valve Specification

The system operating pressure of 130 PSI exceeds the valve's 125 PSI maximum working pressure rating. Even though the difference is only 5 PSI, operating a valve above its rated pressure violates the specification and creates a safety hazard. The valve body, bonnet gasket, and packing are designed for the rated pressure with appropriate safety margins. At 130 PSI, those safety margins are compromised. The plumber needs to either: (1) select higher-rated valves (e.g., 150 or 200 PSI class), (2) verify with the engineer that 125 PSI valves are acceptable with a pressure-reducing station upstream, or (3) use ball valves rated at 600 PSI for sizes 2 inches and under.

Crestline Valve Specification / AWWA C504

Butterfly valves 6 inches and larger require gear operators, not lever handles. An 8-inch butterfly valve with a lever handle is a code violation for two reasons. First, the specification explicitly requires gear operators for valves 2.5 to 12 inches, with gear operators mandatory at 6 inches and above. Second, the torque required to operate an 8-inch butterfly valve against system pressure is too high for safe one-handed lever operation — especially at 7 feet above the floor where an operator would be reaching overhead. Gear operators provide controlled, gradual valve operation that prevents water hammer from rapid closure.

Crestline VFD Specification

The 25-foot cable run exceeds the 20-foot maximum allowed without engineer approval. Long VFD output cables cause reflected wave voltage spikes at the motor terminals that can reach 2-3 times the DC bus voltage, destroying motor winding insulation over time. At 25 feet without mitigation, peak voltage at the motor terminals can exceed the insulation rating of standard motors. The electrician must either: (1) get engineer approval and install an output reactor or dV/dt filter, (2) relocate the VFD closer to the motor, or (3) use an inverter-duty motor rated for the higher voltage peaks.

Crestline VFD Specification / IEEE 519

The 8 kHz carrier frequency is within the allowable range. The specification requires starting at 2 kHz minimum with a maximum of 10 kHz. Higher carrier frequencies reduce audible motor noise (the whining sound) but increase heat generation in the VFD and can increase cable stress. At 8 kHz, this is an acceptable tradeoff for noise-sensitive areas. The electrician should verify the VFD's thermal derating at this frequency and ensure adequate ventilation of the VFD enclosure.

Crestline VFD Specification / NEMA MG-1 Part 31

Crestline specifications limit VFD output cable length to a maximum of 20 feet without specific engineer approval and additional mitigation. Long cable runs cause voltage reflections (reflected wave phenomenon) that can double the peak voltage at motor terminals, destroying motor winding insulation.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.