Crestline Mechanical Specification / SMACNA
What it means on the job
Duct liner is NOT allowed inside kitchen supply ducts, regardless of NRC rating or installation quality. Grease-laden air can saturate fiberglass liner, creating a fire hazard and breeding ground for bacteria. The Crestline spec explicitly prohibits internal duct liner on kitchen supply ductwork. Noise reduction in kitchen duct systems must be achieved through external duct wrap, sound attenuators, or duct silencers mounted upstream of the kitchen branch.
Tested in 1 CraftIQ puzzle
- code-checkKitchen Supply Duct Liner
Related OTHER sections
Crestline Mechanical Specification
Wrong insulation type. While the thickness (0.5 inch) meets the minimum, mineral wool (PI-A) is unacceptable for refrigerant suction lines. The spec requires PI-B (elastomeric/rubber) because refrigerant suction lines operate below the dew point and will condense moisture from the surrounding air. Elastomeric insulation is closed-cell and acts as its own vapor barrier, preventing moisture from reaching the cold pipe. Mineral wool is open-cell and would absorb moisture, lose its insulating value, and cause corrosion on the copper suction line. The wet, degraded insulation would also drip onto equipment and ceiling tiles below.
Crestline Mechanical Specification / ASTM C1136
PVC jacketing is not permitted on outdoor pipe insulation per Crestline specifications. PVC degrades under UV exposure, becomes brittle, and cracks, allowing moisture infiltration that destroys the insulation. Aluminum or stainless steel jacketing is required for outdoor applications.
Crestline Mechanical Specification / California T-24
This installation meets code. In Climate Zone 3, the minimum R-value for supply and return ducts located outside the building is R-8. The contractor correctly used DW-B insulation with a metal jacket, which is required for exterior duct applications to protect the insulation from weather, UV damage, and physical abuse. If this project were in Climate Zone 5 or higher, R-12 would be required instead of R-8.
Crestline Mechanical Specifications
Pre-insulated piping transitions must terminate a minimum of 2'-0" inside the building per the Crestline specifications. At only 1'-0" inside, the transition is too close to the building envelope — moisture can migrate along the pre-insulated carrier pipe from outside, and the joint between pre-insulated and standard piping is exposed to temperature fluctuations from the nearby wall penetration. The 2'-0" minimum ensures the transition is fully within the conditioned space, allowing proper inspection access and preventing condensation issues at the insulation changeover point.
Crestline Mechanical Specifications / ASME B31.9
Ball valves are not permitted underground per the Crestline specifications. All underground valves must be gate valves. Gate valves are preferred underground because they provide a full-port opening with minimal pressure drop when fully open, and their rising stem or position indicator makes it easy to verify valve position from above the valve box. Ball valves underground are problematic because the handle position can be ambiguous through a valve box access, and ball valve seats can be damaged by debris common in underground installations. The ball valve must be replaced with a gate valve of the same size and pressure rating.
Crestline Mechanical Specifications / Site Plan
This installation is correct. Per the Crestline plans, all underground piping not directly outside the central plant is rated for 140 degrees F. The 180 degrees F rating is only required for piping immediately outside the central plant where water temperatures are highest. Building-to-building distribution piping at 140 degrees F rating is appropriate because water temperature drops through the distribution network. The 36" cover also meets the minimum burial depth requirement specified on the detail sheet.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.