CPC 402.0 / California Green Building Standards

What it means on the job

Per CPC 2022, kitchen faucets must default to 1.8 GPM maximum. The temporary increase to 2.2 GPM is permitted only for pot-filling or similar tasks and must require manual activation. The default setting must be 1.8 GPM or less.

Tested in 1 CraftIQ puzzle

  • whats-wrongOffice Breakroom Sink Installation (high-rise office Level 30)
Practice this code — free

Related OTHER sections

CPC 402.0 / ASME A112.18.1

This installation is correct. CPC 2022 requires non-residential lavatory faucets to have a maximum flow rate of 0.5 GPM at 60 PSI. The high-rise office specification matches this requirement. The 0.5 GPM rate is adequate for handwashing and meets California water conservation standards. The ASME A112.18.1 listing confirms the faucets are tested and certified to the applicable standard.

CPC 402.0 / ASME A112.19.2

high-rise office specifications call for 0.125 gallon per flush urinals (pint-flush). A 0.5 GPF urinal uses four times the water required and does not meet California water conservation requirements or the project's LEED enhanced commissioning targets.

CPC 402.0 / ASME A112.19.2 / high-rise office Plumbing Specification

The installed urinals exceed the specified flush volume by 4x. high-rise office requires 0.125 GPF (pint-flush) urinals, not 0.5 GPF. While 0.5 GPF meets the CPC 2022 minimum standard, the project specification is more stringent for LEED water use reduction credits. The contractor must install the 0.125 GPF urinals specified. Using 0.5 GPF urinals would cause the project to fail its LEED water budget calculations and could jeopardize the entire LEED certification.

CPC 604.1 / high-rise office Plumbing Specification

high-rise office specifications require Type L copper for above-floor domestic water piping. Type M has thinner walls and is not rated for the higher pressures found in high-rise buildings. Type K is required for underground installations.

CPC 814.0 / high-rise office Mechanical Specification

Direct connection to the sanitary sewer is not permitted for condensate drains, regardless of whether a P-trap is installed. CPC 814.0 requires condensate to discharge through an indirect waste connection. The high-rise office specification specifically requires the CRAC condensate to spill to a lavatory tailpiece, which provides a visible air gap and ensures the discharge is observable. A direct connection would hide any condensate flow problems and could allow sewer gas to reach the server room if the trap seal is lost. The visible spill point also serves as a diagnostic indicator — if the lavatory is constantly wet, maintenance knows the CRAC is producing excessive condensate.

Crestline BAS Specification

Despite the RTDs being more accurate, they do not meet the specification. The spec requires 10K ohm Type 2 thermistors, not RTDs. This is not about accuracy — it is about standardization and interchangeability. If the building uses 10K Type 2 thermistors throughout, any sensor can be replaced with any manufacturer's 10K Type 2 product without reprogramming the controller. RTDs have a different resistance curve, different wiring (often 3-wire or 4-wire vs. 2-wire), and require different analog input configuration. Mixing sensor types creates a maintenance nightmare.