ASME BPVC Section I PG-71 / ASME B31.1 Section 122.6

What it means on the job

This fails code on multiple counts. First, ASME Section I PG-71.4 prohibits reducing the discharge pipe below the area of the PRV outlet — the 2-inch to 1.5-inch reduction restricts flow and creates excessive back pressure on the PRV, reducing its relieving capacity. Second, the discharge termination at 4 feet above ground level creates a scalding hazard to personnel in the equipment yard; discharge must be directed to a safe location where personnel cannot be exposed to the steam release. Third, the horizontal discharge piping without a drain will accumulate condensate, which can cause water hammer when the PRV lifts. PRV discharge piping must be self-draining with a drip pan elbow or weep hole at the low point per ASME B31.1 Section 122.6.

Tested in 1 CraftIQ puzzle

  • code-checkSteam PRV Discharge Requirements
Practice this code — free

Related ASME sections

ASME B31.9 / IMC 1203.4

Direct connection of copper to steel without a dielectric union or insulating coupling creates a galvanic cell. The dissimilar metals in contact with the electrolyte (water) cause accelerated corrosion of the steel pipe. A dielectric union, brass transition fitting, or insulating coupling is required to prevent galvanic corrosion.

ASME Boiler and Pressure Vessel Code, Section IV — HG-400

ASME BPVC Section IV requires that safety relief valves on hot water boilers be set at or below the maximum allowable working pressure (MAWP), never above it. A valve set at 157.5 psig on a 150 psig rated boiler allows the vessel to be pressurized beyond its design limit before the valve lifts. This defeats the purpose of the safety valve, which is to prevent overpressurization at or before the rated limit. The valve must be replaced with one stamped at 150 psig or lower. This is a mandatory violation that will fail jurisdictional inspection, and the boiler must be taken out of service until corrected.

ASME BPVC Section I PG-71 / ASME B31.1

ASME BPVC Section I and ASME B31.1 require PRV discharge to be piped to a safe location where released steam cannot endanger personnel. Discharge into an occupied walkway creates severe burn and scalding hazards. PRV outlets must be directed vertically upward or to a safe discharge point away from personnel areas.

ASME BPVC Section I PG-71.2

ASME BPVC Section I strictly prohibits any intervening stop valve between a boiler and its pressure relief valve. A closed block valve renders the PRV inoperable, allowing boiler pressure to exceed the maximum allowable working pressure (MAWP) and potentially causing a catastrophic boiler explosion.

ASME BPVC Section IV / ASME B31.1

This fails code. ASME Boiler and Pressure Vessel Code Section IV (Heating Boilers) and ASME B31.1 require a safety relief valve on the low-pressure side of every pressure reducing valve station. The safety valve must be set at or below the MAWP of the downstream equipment (30 PSI in this case). If the PRV fails open, full upstream pressure (150 PSI) would reach equipment rated for only 30 PSI — a catastrophic overpressure event. This is one of the most critical safety lessons taught at every UA local.

ASME BPVC Section IX / ASME B31.1

Per ASME Section IX, a welder qualified on 6-inch pipe is qualified for pipe diameters from 2-7/8 inches and larger (for pipe over 2-7/8" OD test coupons). The 4-inch pipe falls within this range. Since the WPS covers both sizes and the same welding processes are used, this is code-compliant.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.