ASME B31.3 Table A-1 / NACE MR0175
What it means on the job
Carbon steel is not suitable for concentrated sulfuric acid service at elevated temperatures. The acid will cause rapid corrosion and thinning, leading to catastrophic failure. Material selection must follow ASME B31.3 Table A-1 and NACE MR0175 guidelines for corrosive service.
Tested in 1 CraftIQ puzzle
- whats-wrongProcess Piping Installation Errors
Related ASME sections
ASME B31.3 Section 328.5.2 / Section 304.3.3 / Table 341.3.2
Socket-weld construction is poor practice on a 4-inch process line. ASME B31.3 restricts socket welds in the larger sizes: under severe cyclic conditions they are generally limited to NPS 2 and smaller (Table 341.3.2), and socket-welded branch connections are limited to NPS 2 and not more than one-quarter of the header size per Section 304.3.3. Although ASME B16.11 socket-weld fittings are made through NPS 4, butt-weld fittings should be used on 4-inch and larger hazardous-fluid piping to provide full-penetration joints with better strength and radiographic inspectability.
ASME B31.3 Section 341.3.2 / AWS D18.1
Undercut exceeding 1/32 inch (0.8 mm) is a rejectable defect per ASME B31.3 and AWS D18.1. On high-purity systems, undercut creates crevices where contaminants accumulate and bacteria can harbor, compromising system purity.
ASME B31.3 Section 345.4.2
This passes ASME B31.3 requirements. Section 345.4.2 requires the hydrostatic test pressure to be at least 1.5 times the design pressure, corrected for the ratio of allowable stress at test temperature to allowable stress at design temperature. At ambient temperature (approximately 70°F), the allowable stress for most materials is equal to or greater than at 400°F, so the 1.5x multiplier applied to the design pressure of 150 psig gives 225 psig — the minimum acceptable test pressure. The 10-minute hold and subsequent visual inspection at design pressure satisfy the code examination requirements.
ASME B31.9
An expansion joint or compensator only works if the pipe is anchored so that movement is directed INTO it. With no anchors, thermal growth simply travels down the riser and is absorbed by whatever is least able to resist it — a branch connection, a fitting, or a piece of equipment. ASME B31.9 requires piping systems to be anchored and guided so thermal expansion is accommodated by design rather than by chance.
ASME B31.9 — Building Services Piping
Hydronic heating systems require an air separator to remove entrained air. Air in the system causes noise, corrosion, reduced heat transfer, and pump cavitation.
ASME B31.9 §919 and §§920-921
Piping must be independently supported so the pump casing carries no pipe weight or thermal load. ASME B31.9 requires piping to be supported so that stresses are not transmitted to connected equipment. A pump carrying pipe weight goes out of alignment, which destroys the coupling, the seal, and eventually the bearings.
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.