ASHRAE Guideline 36 / Crestline Controls Specification
What it means on the job
Duct temperature probes must be inserted 25-50% of the duct width to obtain a representative reading. Inserting only 10% places the sensor in the boundary layer near the duct wall where temperature is not representative of the airstream, causing inaccurate control.
Tested in 1 CraftIQ puzzle
- whats-wrongDuct Temperature Sensor Installation
Related ASHRAE sections
ASHRAE Guideline 36 — Redundant Equipment Staging
Redundant CRAC units must have one designated as lead and one as lag. Setting both as lead causes both units to run at full capacity simultaneously, wasting energy and eliminating redundancy protection. The Liebert vNSA switch must coordinate lead/lag sequencing so only one unit operates at a time under normal conditions.
ASHRAE Guideline 36 — Section 5.18
Sensors on exterior walls are influenced by solar gain and outdoor temperature conducted through the wall, producing inaccurate space readings. Mount sensors on interior walls per ASHRAE guidelines.
ASHRAE Guideline 36 — Sensor Placement
Temperature sensors must not be placed in direct airflow from supply diffusers. The supply air temperature causes false readings, making the controller unable to maintain proper space temperature setpoint.
ASHRAE Guideline 36 / Manufacturer maintenance requirements
Dirty CRAH coils reduce heat transfer efficiency significantly, potentially losing 20-40% of cooling capacity. Regular coil cleaning is required per ASHRAE maintenance guidelines. Reduced capacity leads to higher server inlet temperatures and potential thermal shutdowns.
ASHRAE Guideline 36 / Manufacturer Requirements
Chillers require a minimum runtime (typically 15-30 minutes) and minimum off-time (typically 15 minutes) to prevent compressor short-cycling. Frequent starts damage the compressor motor and reduce equipment life.
ASHRAE Handbook — Fundamentals, Chapter 7
A thermostat behind a door that is typically held open will be in stagnant air and will not sense the true space temperature. It must be in an area with representative airflow of the occupied zone.