ASHRAE 90.4 / TIA-942

What it means on the job

Branch circuit monitoring is required for capacity planning and to detect load imbalances. ASHRAE 90.4 mandates metering of electrical distribution in data centers, and most Tier III+ designs require per-circuit monitoring.

Tested in 1 CraftIQ puzzle

  • whats-wrongPDU Installation Errors
Practice this code β€” free

Related ASHRAE sections

ASHRAE 90.1-2019, Section 6.5.4.4 (temperature reset) / Section 6.5.4.2 (variable-flow DP reset) / Guideline 36

This chiller plant sequence fails ASHRAE 90.1-2019 Section 6.5.4.4 (Chilled- and Hot-Water Temperature Reset Controls), which requires chilled water supply temperature reset for systems with DDC controls. A fixed 44 degrees F supply temperature forces the chillers to work harder than necessary during mild weather and part-load conditions β€” wasting significant energy (roughly 1-2% per degree F of potential reset). Additionally, the fixed differential pressure setpoint on the variable-flow pumps violates Section 6.5.4.2 (Hydronic Variable Flow Systems), which requires the DP setpoint on DDC variable-flow pumps to be reset downward based on valve positions. Best practice per ASHRAE Guideline 36 likewise resets DP based on the most-open control valve position, reducing pump speed when full design pressure is not needed. Both reset strategies β€” supply water temperature and differential pressure β€” are essential for energy code compliance and efficient chiller plant operation.

ASHRAE 90.1-2019, Section 6.5.4.4 / Guideline 36

This is a proper implementation of chilled water supply temperature reset per ASHRAE 90.1-2019 Section 6.5.4.4 (Chilled- and Hot-Water Temperature Reset Controls) and Guideline 36 Trim and Respond logic. Raising chilled water temperature when loads are low improves chiller efficiency significantly β€” roughly 1-2% per degree F of reset. The valve position-based reset ensures cooling capacity is available when needed.

ASHRAE 90.1-2019, Table 6.5.1.1.3

ASHRAE 90.1 Table 6.5.1.1.3 specifies fixed dry-bulb high-limit shutoff temperatures by climate zone. For Climate Zone 4A, the fixed dry-bulb limit is 75 degrees F. This setup correctly locks out the economizer when outdoor air is too warm to provide free cooling. Differential enthalpy is an alternative method.

ASHRAE Fundamentals Handbook β€” Hydronic System Design

The decoupler (common) pipe connections must be spaced at least 4 to 6 pipe diameters apart so primary and secondary loops are genuinely hydraulically decoupled; at 2 diameters the two loops interact and flow in the common pipe no longer reflects the true surplus or deficit. Note what is NOT the defect here: the absence of isolation valves on the decoupler is CORRECT as installed β€” valving the common pipe would defeat decoupling entirely.

ASHRAE Guideline 13 β€” Alarm Management

Alarms must be prioritized based on severity. A freeze stat alarm (life-safety) should be higher priority than a dirty filter alarm (maintenance). Without prioritization, critical alarms get lost in nuisance alarms, a condition called 'alarm flooding'.

ASHRAE Guideline 13 β€” Data Management

Storing trend data only in field controllers risks data loss when controllers are reset or lose power. Trend data should be archived to the BAS server or a dedicated historian. Controller memory is limited and will overwrite oldest data.