ASHRAE 170 Table 7-1 / FGI Guidelines 2.1-3.2
What it means on the job
This fails on multiple counts. First, ASHRAE 170 Table 7-1 requires a minimum of 12 total ACH in AII rooms — the 10 ACH provided is below the minimum. Second, AII rooms must maintain negative pressure (minimum -0.01 inches w.g.) relative to adjacent spaces, which requires the exhaust rate to exceed the supply rate — not equal it. Neutral pressure provides no directional airflow control and allows infectious aerosols to escape when doors open. Third, while HEPA filtration on the exhaust is good practice, it does not compensate for inadequate air changes or incorrect pressure relationships. The room as designed would not contain airborne pathogens.
Tested in 1 CraftIQ puzzle
- code-checkIsolation Room Pressure Requirements
Related ASHRAE sections
ASHRAE 15 §9.9 (Pressure-Limiting Devices)
Head pressure of 165 psig is 40 psig above design, directly caused by the reversed condenser water piping. Watch the authority: the high-pressure cutout setting comes from ASHRAE 15 §9.9 and is referenced to the vessel design pressure, NOT to a universal number — there is no "trips at 175 psig" rule in any standard, and AHRI 550/590 is a performance-rating standard containing no safety-control provisions at all. Running this far above design costs compressor power and pushes the machine toward a nuisance high-pressure trip.
ASHRAE 170 Table 7-1
The air change rates are right but the pressure direction is backwards. ASHRAE 170 Table 7-1 requires an airborne infection isolation room to be NEGATIVE relative to adjacent spaces — exhaust must exceed supply so air flows INTO the room and is exhausted, keeping airborne pathogens from spilling into the corridor. The room protects everyone outside it from the patient. Positive pressure is what a protective environment (PE) room uses, which protects an immunocompromised patient FROM the building. The two room types have the same 12 total / 2 outdoor ACH and opposite pressure directions, which is exactly why they get mixed up. Get the direction wrong and the isolation room does the opposite of its job.
ASHRAE 170 Table 7-1 / FGI Guidelines
This passes all code requirements. ASHRAE 170 Table 7-1 specifies an OR temperature range of 68-75°F and a relative humidity range of 20-60%. The facility's 72°F and 45% RH are well within both ranges. The visible display allows the surgical team to verify conditions during procedures. The alarm capability ensures staff are notified if conditions drift out of range. The dedicated AHU with cooling, reheat, and humidification provides the three-stage control needed to simultaneously manage temperature and humidity — essential because cooling the air also removes moisture, requiring separate reheat and humidification stages.
ASHRAE 189.1 §6.3.2 (drift eliminators: 0.002% counterflow / 0.005% crossflow of recirculating water flow); CTI ATC-140 Isokinetic Drift Test Code
Damaged drift eliminators allow excessive water loss through carryover of water droplets into the discharge airstream. This wastes water and chemical treatment, and can create safety hazards from ice formation on nearby surfaces in winter. Drift loss should be limited to 0.001-0.005% of circulating flow per ASHRAE.
ASHRAE 62.1
ASHRAE 62.1 requires outdoor air determined by the ventilation-rate procedure — for offices, 5 CFM per person plus 0.06 CFM per square foot — not an arbitrary fixed percentage. Run the numbers: 20 occupants need 100 CFM of people-OA plus the floor-area component (a 2,000 sq ft zone adds 120 CFM, totaling ~220 CFM). Whether '15% OA' delivers that depends entirely on the unit's supply airflow — a 2,000 CFM unit at 15% provides 300 CFM (passes), a 1,200 CFM unit provides 180 CFM (fails). A percentage setpoint with no calculation behind it isn't a compliant ventilation design.
ASHRAE 62.1 — Section 6.2 (Ventilation Rate Procedure)
Minimum outdoor air position must meet the zone ventilation requirements of the Ventilation Rate Procedure during occupied mode — it can never be 0%. ASHRAE 62.1 ventilation rates apply whenever the space is occupied, so a 0% minimum during occupancy starves the space of required outdoor air and is a code violation. (0% is only acceptable during UNOCCUPIED periods, where ASHRAE 90.1 actually encourages closing the OA damper to save energy.)
CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.