ASHRAE 135 (BACnet) — Object Types

What it means on the job

Connecting a 0-10VDC analog output signal to a binary (digital) input terminal will not control the device properly. Binary inputs only read on/off states. Analog signals must connect to analog input terminals for proportional control.

Tested in 1 CraftIQ puzzle

  • whats-wrongDDC Controller Wiring Panel
Practice this code — free

Related ASHRAE sections

ASHRAE 135 (BACnet) — Clause 6.1

Network number 0 is reserved and means 'local network only' in BACnet. A routed segment must have a unique non-zero network number (1-65534) assigned. Using 0 prevents the router from forwarding messages to and from this segment.

ASHRAE 135 (BACnet) — Clause 9, MS/TP MAC addressing

MS/TP reserves MAC 255 for broadcast and 128-254 for slave devices; 127 is the very top of the master range. Parking a field controller at 127 forces max_master to its ceiling, so every token rotation polls the entire 0-127 address space looking for masters that aren't there — network performance craters. Keep field controllers in a contiguous low range and set max_master just above the highest used address.

ASHRAE 135 (BACnet) — MS/TP Physical Layer

BACnet MS/TP requires a daisy-chain (bus) topology, not star topology. Star wiring creates signal reflections and communication failures. Each device must connect in series on the bus.

ASHRAE 135-2016

A BACnet gateway does not satisfy a native BACnet requirement. The specification explicitly requires BACnet per ASHRAE 135-2016 and prohibits proprietary protocols. A gateway creates a single point of failure, adds latency, limits functionality (not all BACnet services translate through gateways), and locks the owner into one vendor for the field-level devices. Native BACnet means every controller communicates BACnet natively — either BACnet/IP or BACnet MS/TP — without translation. This is a critical specification requirement designed to protect the building owner from vendor lock-in.

ASHRAE 135-2016 / Crestline BAS Specification

Crestline specifications require all building automation systems to comply with ASHRAE Standard 135-2016 (BACnet). Proprietary, closed-protocol systems lock the owner into a single vendor and prevent competitive service and integration. Open-protocol BACnet is mandatory for all new installations.

ASHRAE 170 Table 7-1

This installation meets ASHRAE 170 Table 7-1 requirements for operating rooms. The standard requires a minimum of 20 total ACH with at least 4 ACH of outdoor air. The positive pressure relationship to corridors prevents unfiltered corridor air from entering the sterile environment. HEPA filtration and laminar flow delivery over the surgical table are best practices aligned with FGI Guidelines Section 2.1-3.2 for reducing surgical site infection risk. All specified parameters are at or above the minimum code requirements.

CraftIQ explanations are original educational commentary written in trade language and verified against the cited standards. Always confirm requirements against the code edition adopted by your jurisdiction — this is training material, not a substitute for the code book or your AHJ.