ASHRAE 135 (BACnet) — Object Types
What it means on the job
Connecting a 0-10VDC analog output signal to a binary (digital) input terminal will not control the device properly. Binary inputs only read on/off states. Analog signals must connect to analog input terminals for proportional control.
Tested in 1 CraftIQ puzzle
- whats-wrongDDC Controller Wiring Panel
Related ASHRAE sections
ASHRAE 135 (BACnet) — Clause 6.1
Network number 0 is reserved and means 'local network only' in BACnet. A routed segment must have a unique non-zero network number (1-65534) assigned. Using 0 prevents the router from forwarding messages to and from this segment.
ASHRAE 135 (BACnet) — Clause 9, MS/TP MAC addressing
MS/TP reserves MAC 255 for broadcast and 128-254 for slave devices; 127 is the very top of the master range. Parking a field controller at 127 forces max_master to its ceiling, so every token rotation polls the entire 0-127 address space looking for masters that aren't there — network performance craters. Keep field controllers in a contiguous low range and set max_master just above the highest used address.
ASHRAE 135 (BACnet) — MS/TP Physical Layer
BACnet MS/TP requires a daisy-chain (bus) topology, not star topology. Star wiring creates signal reflections and communication failures. Each device must connect in series on the bus.
ASHRAE 135-2016
A BACnet gateway does not satisfy a native BACnet requirement. The specification explicitly requires BACnet per ASHRAE 135-2016 and prohibits proprietary protocols. A gateway creates a single point of failure, adds latency, limits functionality (not all BACnet services translate through gateways), and locks the owner into one vendor for the field-level devices. Native BACnet means every controller communicates BACnet natively — either BACnet/IP or BACnet MS/TP — without translation. This is a critical specification requirement designed to protect the building owner from vendor lock-in.
ASHRAE 135-2016 / Crestline BAS Specification
Crestline specifications require all building automation systems to comply with ASHRAE Standard 135-2016 (BACnet). Proprietary, closed-protocol systems lock the owner into a single vendor and prevent competitive service and integration. Open-protocol BACnet is mandatory for all new installations.
ASHRAE 15
ASHRAE 15 requires a refrigerating machinery room to be separated from the rest of the building with tight-fitting, self-closing doors. The room is designed to contain a refrigerant release and exhaust it to the outdoors. Wedging the doors open defeats the containment and lets a release migrate into occupied space.